The SNMP hardware type enables control of power distribution units of the type frequently found in data centre racks. PDUs frequently have a management ethernet interface and SNMP support enabling control of the power outlets.
The SNMP power interface works with the PXE boot interface for network deployment and network-configured boot.
Note
Unlike most of the other power interfaces, the SNMP power interface does
not have a corresponding management interface. The SNMP hardware type uses
the fake
management interface instead.
This is a non-exhaustive list of supported devices. Any device not listed in this table could possibly work using a similar driver.
Please report any device status.
Manufacturer | Model | Supported? | Driver name |
---|---|---|---|
APC | AP7920 | Yes | apc_masterswitch |
APC | AP9606 | Yes | apc_masterswitch |
APC | AP9225 | Yes | apc_masterswitchplus |
APC | AP7155 | Yes | apc_rackpdu |
APC | AP7900 | Yes | apc_rackpdu |
APC | AP7901 | Yes | apc_rackpdu |
APC | AP7902 | Yes | apc_rackpdu |
APC | AP7911a | Yes | apc_rackpdu |
APC | AP7921 | Yes | apc_rackpdu |
APC | AP7922 | Yes | apc_rackpdu |
APC | AP7930 | Yes | apc_rackpdu |
APC | AP7931 | Yes | apc_rackpdu |
APC | AP7932 | Yes | apc_rackpdu |
APC | AP7940 | Yes | apc_rackpdu |
APC | AP7941 | Yes | apc_rackpdu |
APC | AP7951 | Yes | apc_rackpdu |
APC | AP7960 | Yes | apc_rackpdu |
APC | AP7990 | Yes | apc_rackpdu |
APC | AP7998 | Yes | apc_rackpdu |
APC | AP8941 | Yes | apc_rackpdu |
APC | AP8953 | Yes | apc_rackpdu |
APC | AP8959 | Yes | apc_rackpdu |
APC | AP8961 | Yes | apc_rackpdu |
APC | AP8965 | Yes | apc_rackpdu |
Aten | all? | Yes | aten |
CyberPower | all? | Untested | cyberpower |
EatonPower | all? | Untested | eatonpower |
Teltronix | all? | Yes | teltronix |
pysnmp
or python-pysnmp
Add snmp
to the list of enabled_hardware_types
in ironic.conf
.
Also update enabled_management_interfaces
and
enabled_power_interfaces
in ironic.conf
as shown below:
[DEFAULT]
enabled_hardware_types = snmp
enabled_management_interfaces = fake
enabled_power_interfaces = snmp
To set the default boot option, update default_boot_option
in
ironic.conf
:
[DEFAULT]
default_boot_option = netboot
Note
Currently the default value of default_boot_option
is netboot
but it will be changed to local
in the future. It is recommended
to set an explicit value for this option.
Note
It is important to set boot_option
to netboot
as SNMP hardware
type does not support setting of boot devices. One can also configure
a node to boot using netboot
by setting its capabilities
and
updating Nova flavor as described below:
openstack baremetal node set --property capabilities="boot_option:netboot" <node-uuid>
openstack flavor set --property "capabilities:boot_option"="netboot" ironic-flavor
Restart the Ironic conductor service.
service ironic-conductor restart
Nodes configured to use the SNMP hardware type should have the driver
field
set to the hardware type snmp
.
The following property values have to be added to the node’s
driver_info
field:
snmp_driver
: PDU manufacturer driversnmp_address
: the IPv4 address of the PDU controlling this node.snmp_port
: (optional) A non-standard UDP port to use for SNMP operations.
If not specified, the default port (161) is used.snmp_outlet
: The power outlet on the PDU (1-based indexing).snmp_version
: (optional) SNMP protocol version
(permitted values 1
, 2c
or 3
). If not specified, SNMPv1
is chosen.snmp_community
: (Required for SNMPv1 and SNMPv2c) SNMP community
parameter for reads and writes to the PDU.snmp_security
: (Required for SNMPv3) SNMPv3 User-based Security Model
(USM) user name.The following command can be used to enroll a node with the snmp
hardware
type:
openstack baremetal node create --os-baremetal-api-version=1.31 \
--driver snmp --driver-info snmp_driver=<pdu_manufacturer> \
--driver-info snmp_address=<ip_address> \
--driver-info snmp_outlet=<outlet_index> \
--driver-info snmp_community=<community_string> \
--properties capabilities=boot_option:netboot
This version of the SNMP power interface does not support SNMPv3 authentication
or encryption features. When using SNMPv3, the SNMPv3 agent at the PDU must
be configured in noAuthNoPriv
mode. Also, the snmp_security
parameter
is used to configure SNMP USM user name to the SNMP manager at the power
interface. The same USM user name must be configured to the target SNMP agent.